Sie befinden Sich nicht im Netzwerk der Universität Paderborn. Der Zugriff auf elektronische Ressourcen ist gegebenenfalls nur via VPN oder Shibboleth (DFN-AAI) möglich. mehr Informationen...
Theoretical Calculation of Inrush Currents in Three- and Five-Legged Core Transformers
Ist Teil von
IEEE transactions on power delivery, 2007-04, Vol.22 (2), p.986-995
Ort / Verlag
New York, NY: IEEE
Erscheinungsjahr
2007
Quelle
IEEE Electronic Library (IEL)
Beschreibungen/Notizen
In this paper, a theoretical study of the three-phase transformer behavior in the presence of a sag is presented by considering that the fault clearing is produced simultaneously in all phases. Analytical expressions of the magnetic flux and the inrush current after voltage recovery are obtained, and the results presented in the literature are analytically justified. The influence of depth, duration, and the initial point-on-wave on the peak value of the inrush current are studied for all sag types. Simple expressions to obtain the value of the current peaks are presented