Theoretical and basic experimental analysis on load adjustment of geothermal heat pump systems
Ist Teil von
Energy conversion and management, 2003, Vol.44 (1), p.1-9
Ort / Verlag
Oxford: Elsevier Ltd
Erscheinungsjahr
2003
Link zum Volltext
Quelle
Alma/SFX Local Collection
Beschreibungen/Notizen
In order to match the output capacity of a geothermal heat pump system (GHPS) with the actual load requirement, research has been conducted in searching for suitable adjusting methods for the GHPS and on the subsequent effects on the working parameters of the GHPS. Firstly, several methods are compared, and it is found that the method of adjusting the compressor's rotation speed using a transducer is better than the others. Secondly, this method is experimented on a small scale GHPS at frequencies ranging from 30 to 55 Hz. The analysis of the experimental data reveals the relationships between the compressor frequency and other important parameters, such as coefficient of performance, heat capacity, cool capacity and compressor power input. The conclusions in the paper can serve as some guidance to the load adjustment of GHPS.