Thermal comfort and self-reported productivity in an office with ceiling fans in the tropics
Ist Teil von
  • Building and environment, 2018-05, Vol.135, p.202-212
Ort / Verlag
Oxford: Elsevier Ltd
Erscheinungsjahr
2018
Quelle
Alma/SFX Local Collection
Beschreibungen/Notizen
  • Here we present a field study examining the impact of elevated room temperature and air movement on thermal comfort and self-reported productivity. This experiment was performed in three environmental conditions (one with a set-point of 23 °C—a typical set-point used in Singapore—and two elevated (up to 28 °C) room temperature conditions). Occupants had shared control of ceiling fans. The results show that the most comfortable thermal condition, with thermal sensation closest to neutral, is achieved at a room temperature of 26 °C with operating fans. Increasing the temperature set-point from 23 °C to 26 °C resulted in a significant increase in thermal acceptability (from 59% to 91%), and a 44 kWh/m2yr savings in electrical energy used for comfort cooling. We found that a room's set-point temperature can be increased up to 27 °C without creating a negative impact when controllable air movement is provided compared to an environment with a set-point of 23 °C. Thermal satisfaction is significantly higher in spaces of 26 °C with operating fans, than when the room's temperature is set at the typical 23 °C. Moreover, the relative humidity in the office is decreased from 62% (when the temperature was 23 °C) to 50% when the temperature was 27 °C. Occupant's self-reported ability to concentrate, be alert, and ability to be productive was comparably high in all conditions. The results indicate that work performance is poorly correlated with room temperature, but increases with greater individual thermal satisfaction. •The most comfortable conditions are achieved at a temperature of 26 °C with fans.•Ceiling fans provide neutral thermal sensation in real office environments with temperatures up to 27 °C.•Room relative humidity decreases with the increase of a room's temperature set-point.•Self-reported productivity is highest in conditions supporting neutral thermal sensation.•Self-reported productivity increases with an increase in occupants' thermal satisfaction.
Sprache
Englisch
Identifikatoren
ISSN: 0360-1323
eISSN: 1873-684X
DOI: 10.1016/j.buildenv.2018.03.013
Titel-ID: cdi_proquest_journals_2077077887

Weiterführende Literatur

Empfehlungen zum selben Thema automatisch vorgeschlagen von bX