2007 IEEE International Symposium on Circuits and Systems (ISCAS), 2007, p.2431-2434
Ort / Verlag
IEEE
Erscheinungsjahr
2007
Quelle
IEEE Electronic Library Online
Beschreibungen/Notizen
This paper addresses the effect of distributed generators, specifically squirrel cage induction generators, on 3-ϕ bolted short-circuit fault currents to make sure that they do not interfere with the interruption capability of circuit breakers. Results of a laboratory experiment, and simulation results for 16 different induction machines, including their feeder and transformer connections to the substation, are presented for a short-circuit at the substation site. An equation was developed for the upper boundary envelope of the current peaks contributed by the induction generators, and was used for successful comparison with simulation results.