Sie befinden Sich nicht im Netzwerk der Universität Paderborn. Der Zugriff auf elektronische Ressourcen ist gegebenenfalls nur via VPN oder Shibboleth (DFN-AAI) möglich. mehr Informationen...
Electronics and electromechanics, 2020-01 (3), p.24-30
2020
Volltextzugriff (PDF)

Details

Autor(en) / Beteiligte
Titel
ACTIVE SHIELDING OF EXTERNAL MAGNETIC FIELD OF BUILT-IN TRANSFORMER SUBSTATIONS
Ist Teil von
  • Electronics and electromechanics, 2020-01 (3), p.24-30
Ort / Verlag
Kharkiv: Department of Electrical Apparatus of National Technical University, Kharkiv Polytechnic Institute
Erscheinungsjahr
2020
Quelle
Free E-Journal (出版社公開部分のみ)
Beschreibungen/Notizen
  • This paper deals with the mitigation of low-frequency magnetic field of build-in transformer substations down to the reference level 0.5 [micro]T in nearby living spaces. To meet the reference level, we substantiate the actuality of the usage of active shielding methods having higher efficiency, comparably to metal consuming passive shielding. We show that the optimization of parameters and localization of compensation coils is the main goal of the synthesis of the active shielding system. The solution of synthesis problem is based on the developed 3D numerical model by using particles multiswarm optimization algorithms from Pareto-optimal solutions set taking into account binary preference relations. This allows justifying the usage of simple active shielding system for magnetic field mitigation down to the reference level in living spaces, located near build-in transformer substations (2 * 400 kVA, 6/0.4 kV). The synthesized active shielding system has two plane compensation coils installed near the ceiling (wall) of the substation room. The area of each coil is less than 10 [m.sup.2] and the number of ampere-turns is less than 30. We show that the efficiency of the active shielding system is 6 when it electric power consumption is less than 100 W. This allows mitigating the magnetic field down to 0.5 [micro]T in 40 [m.sup.2] living space located on top or side from the substation. The application of synthesized active shielding system (subject to the positive results of experimental studies of their full-scale physical models) allows solving the actual and socially significant problem of the health protection of tenants of residential buildings with build-in transformer substations from the negative effects of power frequency magnetic field. References 16, tables 2, figures 8.
Sprache
Englisch; Ukrainisch
Identifikatoren
ISSN: 2074-272X
eISSN: 2309-3404
DOI: 10.20998/2074-272X.2020.3.04
Titel-ID: cdi_doaj_primary_oai_doaj_org_article_6d060bb201e44838bd458bef563a5bd1

Weiterführende Literatur

Empfehlungen zum selben Thema automatisch vorgeschlagen von bX