Sie befinden Sich nicht im Netzwerk der Universität Paderborn. Der Zugriff auf elektronische Ressourcen ist gegebenenfalls nur via VPN oder Shibboleth (DFN-AAI) möglich. mehr Informationen...
Effect of floor level slit exhaust ventilation system on distribution of house dust
Ist Teil von
Journal of Central South University, 2012-03, Vol.19 (3), p.696-702
Ort / Verlag
Heidelberg: Central South University
Erscheinungsjahr
2012
Quelle
Alma/SFX Local Collection
Beschreibungen/Notizen
Based on the fact that the house dust usually falls on the ground, the floor level slit exhaust ventilation system including inlet located at the ceiling and outlet of slit exhaust installed at comer between wall and floor was considered. Experiments and simulations were performed to investigate the flow and diffusion fields that are affected by this floor level slit exhaust ventilation system. The characteristics of airflow with experiments and computation fluid dynamics (CFD) are generally similar except airflow at the location of impinging flow and the location right below the inlet. Riboflavin particles were used as the house dust. For the spatial distribution of riboflavin particles in the ventilation system before operation, due to the influence of gravity, different sizes of particles show smooth decay curve. After floor level slit exhaust ventilation system is operated, the decay rate of the particles becomes faster than that after the ventilation system is powered on, and the particles with diameter of 0.5-3.0 μm in the experimental data and calculated values show good agreement.